Ba20-AI/I Acrel 12vdc Electric Current Transducers Analog 4-20ma Modbus Rtu
Contact Person : Dina Huang
Phone Number : 18761502682
WhatsApp : +8618761502682
Detail Information |
|||
Usage: | Current Transmitter | Output: | 4-20mA |
---|---|---|---|
Power Supply: | DC24V Or DC12V | Accuracy: | 0.5 |
Installation: | Din Rail | Single Gross Weight: | 0.900 Kg |
Package Type: | Paper Carton | ||
Highlight: | acrel ac current transducer,0-5v ac current transducer,din rail 4 20ma current transducer |
Product Description
General
BD series DC voltage sensors are the measuring module that converts the measured DC voltage into the proportional DC current or DC voltage signal according to the optical isolation theory. The input side is highly insulated from the output side.
High accuracy, linearity and integration, small size, simple structure, long-term stability and adaptability to various working conditions. They are widely used for system control and detection of electrical equipment in the power, petroleum, mine, chemical, railway, communication, building automation sectors.
Explanation for type
Note: BA50L-AI/I(V): alternating residual current sensor
Technical data
Technical parameters | Index | |
Input signal | BA50-AI/I measuring range AC0~(60-600)A | |
Output | Nominal value | DC4-20mA or DC0-20mA |
Overload protection | Max.output≤135% of full scale | |
Load resistance | when current output:(supply voltage-4/0.02)Ω | |
Ripple component | AC component of the output signal≤1% of full scale | |
Power supply |
DC24V allowed range 18~30V DC12V allowed range 10~15V |
|
Power consumption | ≤1W | |
Dielectric strength | Power frequency withstans voltage 2000VAC between input/output and power supply | |
Pricision degree | 0.5 | |
Temperature drift coefficient | ≤200ppm | |
Response time | Average≤350mS | |
Installation method | TS35mm guide installation,or screw in cabinet | |
Ambient conditions | Temperature |
Operating temperature:-25℃~+70℃ Storage temperature:-40℃~+85℃ |
Humidity | ≤90%RH,no dew,no aggressive gas | |
Altitude | ≤2500m |
Shape and hole size
The shape and hole size of BA50 current transformer.
Type | Outline size(mm) | |||||
W | H | φ | M | N | L | |
BA50-AI/I | 35 | 84 | 50 | 125 | 135 | 24 |
Example of Wiring
As shown in the figure,the input is lac.The output of current output sensor is the current source with common GND while the output of voltage output sensor is the voltage source with common GND.In this example,RL is the user load.If the output is current,the load is up to 400Ω(with 12V power supply) or 800Ω(with 24V power supply). If the output is voltage,the load is 1kΩ or above.
Acrel Co., Ltd. [Stock Code: 300286.SZ] is one of the few leading companies in China who provides various systematic solutions of power monitoring, power control, energy management and electrical safety for smart grid users.
Since June 2003, we has always been focused on the research, production and sales of intelligent electric meters. We concentrates on providing products and services to help customers improve electricity efficiency and safety. So far we had the following comprehensive solutions for different applications: 35(10)/0.4kV substation automation system, building mounted photovoltaic (BMPV) system, power quality management system, energy management system, electrical fire monitoring system, IT distribution system for medical locations, precise distribution management system, power supply monitoring system for fire protection equipment, fire emergency lighting and evacuate indicating system, fire resistant doorsets monitoring system, smart lighting control system, Lithium battery management system and electric vehicle charging system.
Certificate
Shipping
Enter Your Message